FIFO Load FFL

At the right of a rung in a program's ladder routine. Not in a Logic Class. Placing it creates its control tag.

TagAfter two scans
FFL1LEN 8 POS 1 EN 1 DN 0 EM 0 FU 0
FFL1_Data[0, 0, 0, 0, 0, 0, 0, 0]
FFL1_Execute1
FFL1_Reset0

How it works

Each time Execute turns on, writes Source at the end of the queue, the element at POS, and adds 1 to POS. The oldest entry stays at element 0, so FIFO Unload hands entries on in the order they went in. A full queue is left as it is.

Status bits

The Control tag holds the state. Read a bit with the tag name and a dot, such as Control.DN.

BitMeaning
.ENOn while the Execute of the load is on.
.EUOn while the Execute of the unload is on. It is there once an unload uses this Control tag.
.EMEmpty: on while POS is 0.
.FUFull: on while POS equals LEN.
.DNDone: on while the queue is full, the same as FU.
.LENLength: how many entries it can hold. It cannot be more than the size of the array.
.POSPosition: how many entries are in the queue. The next load writes to this element of the array.

Rules

  • A queue acts once when Execute turns on, not on every scan. If Execute is already on in the first scan, it acts once then.
  • A load into a full queue does nothing and raises no fault, so the value is lost.
  • An unload from an empty queue does nothing and leaves Dest as it was.
  • Reset sets POS to 0 and does not clear the array. The old values stay in the array until they are written over.
  • The oldest entry is at element 0. FIFO Unload takes it from there.

Over time

A FIFO Load with Execute on for scans 2 and 3, off at scan 4, then on for scans 5 to 7. POS moves one step at scan 2 and one at scan 5, each time Execute turns on. Holding Execute on adds no steps.Scan12345678Execute.EN.POS011122222 Execute turns on: one step3 Held on: no step5 Turns on again: next step
ScanExecute.EN.POS
1OffOff0
2OnOn1
3OnOn1
4OffOff1
5OnOn2
6OnOn2
7OnOn2
8OffOff2

The chart shows a FIFO Load; the others act on Execute the same way. One step happens on the scan where Execute turns on. Holding Execute on does nothing more, so turn it off and on for the next step.

How it's used

Use FFL to line parts up for a station that takes them in the order they arrived. This queue holds 2.

1. Load 11. Execute was already on in the first scan, and it loaded once. 11 is at position 0 and POS is 1.

StepPartQueueInfeed.POSInfeed.FUInfeed.DN
1. Load 1111[11, 0]100
2. Hold Load on11[11, 0]100
3. Turn Load off11[11, 0]100
4. Load 2222[11, 22]211
5. Turn Load off22[11, 22]211
6. Load 3333[11, 22]211
7. Reset33[11, 22]000

The queue went [0, 0] to [11, 0] to [11, 22]. The third load found it full, so 33 was lost and POS stayed 2. Reset set POS to 0 and left 11 and 22 in the array.

Operands

OperandWhat it is forData typeRead or write
ExecuteA BOOL that makes the instruction act once each time it turns on.BOOLReads
ResetA BOOL that, while on, clears the control tag and starts over.BOOLReads
SourceThe value added to the queue.BOOL, DINT, REAL or a numberReads
ArrayThe array that holds the queue.Array of BOOL, DINT, REALWrites
ControlThe CONTROL tag that tracks the position, length and status.CONTROLReads and writes

Common mistakes

  • Holding Execute on and expecting more loadsA load happens once each time Execute turns on. Turn it off and on again for the next entry.
  • Rung already true on the first scanA rung that is already true on the first scan after a reset acts once, the same as any other scan where Execute turns on.