Fail-safe stop

A real Stop button is wired normally closed. Its input is on until the button is pressed, and the rung reads it with XIC.

Step by step

Pick a step. The rungs are drawn by the editor after Core scans the program up to that step.

1. Press StartPB. StopOK is 1 because the Stop circuit is closed. XIC StopOK passes power and Motor turns on.

StepStartPBStopOKMotor
1. Press StartPB111
2. Release StartPB011
3. Press Stop000
4. Release Stop, press StartPB111
5. Wire breaks000
6. Press StartPB100

Why it works

  • The input is on in the healthy state. Anything that breaks the circuit, the button, a loose terminal or a cut cable, turns it off.
  • XIC passes power only while its tag is 1, so it passes only while the Stop circuit is healthy.
  • Name the tag for the healthy state, such as StopOK, so XIC reads naturally.

Common mistakes

  • A normally open Stop read with XIOIt works while the wiring is good, but a broken wire means Stop can never be seen. The machine keeps running.
  • Using this for an emergency stopAn emergency stop must cut power through a safety circuit, not only through the PLC program. These lessons are not a safety system.