Latch and reset

OTL turns the alarm on. OTU turns it off, but only when the operator resets and the cause is gone.

Step by step

Pick a step. The rungs are drawn by the editor after Core scans the program up to that step.

1. HighLevel on. Rung 0 is true and OTL sets Alarm to 1.

StepHighLevelResetPBAlarm
1. HighLevel on101
2. Press ResetPB111
3. HighLevel off001
4. Press ResetPB010
5. Release ResetPB000

Why it works

  • OTL writes 1 when its rung is true and writes nothing when it is false. That is why Alarm stays on after HighLevel clears.
  • OTU is the only thing that writes 0. It needs ResetPB and the XIO on HighLevel, so a reset cannot clear an alarm whose cause is still there.
  • OTL and OTU work on the same tag. If both rungs were true in one scan, the one lower down would win, because it writes last.

Common mistakes

  • Reset without checking the causeWithout XIO HighLevel, holding Reset clears the alarm and the next scan sets it again. The operator never sees it stay on.
  • OTE for an alarmAn OTE alarm turns off as soon as the cause clears, so a short fault is never seen.

Instructions used